Abstract
In this paper, the potential for time series classifiers to identify faults and their location in a DC Microgrid is explored. Two different classification algorithms are considered. First, a minimally random convolutional kernel transformation (MINIROCKET) is applied on the time series fault data. The transformed data is used to train a regularized linear classifier with stochastic gradient descent (SDG). Second, a continuous wavelet transform (CWT) is applied on the fault data and a convolutional neural network (CNN) is trained to learn the characteristic patterns in the CWT coefficients of the transformed data. The data used for training and testing the models are acquired from multiple fault simulations on a 750 VDC Microgrid modeled in PSCAD/EMTDC. The results from both classification algorithms are presented and compared. For an accurate classification of the fault location, the MINIROCKET and SGD Classifier model needed signals/features from several measurement nodes in the system. The CWT and CNN based model accurately identified the fault location with signals from a single measurement node in the system. By performing a self-learning monitoring and decision making analysis, protection relays equipped with time series classification algorithms can quickly detect the location of faults and isolate them to improve the protection operations on DC Microgrids.
AI Summary
This paper addresses fault-location identification in a DC microgrid by treating measured voltage and current waveforms as time-series data rather than independent samples. It compares two approaches: MINIROCKET followed by a stochastic-gradient linear classifier, and a Continuous Wavelet Transform that converts the signals into time-frequency patterns for classification with a convolutional neural network. Using simulated fault events from a 750 V DC microgrid, the MINIROCKET approach achieves about 99% location accuracy when measurements from many nodes are available, but its accuracy drops when only one measurement location is used. The CWT-CNN approach identifies fault location with 100% accuracy using signals from a single node in the reported tests. The results show that the appropriate protection architecture depends on measurement availability: distributed measurements favor the lighter MINIROCKET method, while the CNN approach can extract location information when sensing is sparse.
Full Paper
The full paper is available from the publisher or an authoritative repository.
View Published Version ↗